中文 | English  
 
Detail    
 
 
  
AC Series Compensation De-icing Device
AC Series Compensation De-icing Device

General
     The device includes the following equipments: high voltage series capacitors, series reactor, discharge coil, zinc oxide arrester, grounding switch, electric display device, connect wires, post insulators, installed framework;
Its working principle: The devices is connected with line required ice melting in series, to adjust its capacitance to match line inductance and make the line current up to the melting of ice required current, through power supply of interval outline at 10kV substation, after running of certain time, the wires heat will melt the ice build-up online on the road, to play the role of melting ice.
Main Features
Simple structure, low cost;
Capacitance adjustment range large , the wiring simple, flexible;
Because of circuit inductance to compensate, making the ice melting power consumption efficiency to achieve energy saving purposes;
Direct power supply with a 10kV substation, the program advanced;
Capacitor lying down layout, small size;
Technical parameters (for example)
such as: TCB8.7-26100/290
Models and the meaning of
T: complete sets of equipment
CB: Series Compensation
8.7: Series capacitor's rated voltage 8.7kv
26100: device rated capacity 26100kvr (three-phase )
290: single-phase capacitor unit rated capacity for the 290kvr
Rated capacity: 261000kvr
Actual device capacity: according to the required subscriber capacitance parameters, choose line wiring , when a certain connection mode, the device's capacity is set, its value line parameters can be calculated.
Rated capacitance: 8.7Ω
Rrated capacity: 366.1uF
Actual capacitance: According to some of the wiring of the capacitor obtained the actual capacitance.
Rated capacity: 8.7Mvar
Capacitor insulation level: 65/125kv
Capacitor Connection: connected with transmission lines in series
Wiring: 10 in parallel and 3 in series (Transmission Line Series Capacitor Compensation Device has three phases, each with sub- three-tier arrangement, each floor consists of 10 capacitors units); each layer of the capacitor unit can have 7 ways of wiring.
Discharge resistor: Capacitor discharge equipped with internal resistance, disconnect from the grid, the terminal voltage can be reduced within 10 minutes to 75 volts.
Service Conditions
Altitude: ≤ 2000m
Ambient temperature type: -40 / D
Installation Location: Outdoor
Relative humidity (at 25 ° C,) on day average: 95% , monthly average: 90%
Earthquake intensity: 8 degree ,  horizontal acceleration: 0.3g, vertical acceleration: 0.2g
Assumed ice thickness: 5mm (wind speed not more than 15m / s)
Nominal system voltage: 10kv
System rated frequency: 50Hz
The switch used in capacitor bank must be un-reusable breakdown of vacuum circuit breakers

 

 
 
 